Traycana new logo black
woodward logo

ESSB-3

SKU: SA-4478
In stock

Description

Product Overview

The EPS 1000 is a programmable,
three-channel equipment protection
module designed to perform a
variety of functions simultaneously.
It is especially suited for engine
protection, sequenced operations,
and critical timing applications. It
can also be used for unattended
engine starting using autocrank
and glow plug functions.

Key Features

  • PC programmable, microprocessor based for
    accurate and stable set points
  • Two-piece enclosure allows either recessed panel
    mounting or base mounting (Patent applied for)
  • Front panel LED’s provide instant visual data on
    operational status
  • Three output channels for independent configuration
    of various actions
  • Each channel can be configured in one of three
    modes:
    1. Speed Switch
    2. Autocrank Controller
    3. Glow Plug Controller
  • Speed signal input is user selectable for magnetic
    pickup, ignition, or Hall Effect sensor
  • Autocrank mode allows programming for crank time,
    rest time, and maximum crank attempts
  • Glow plug mode controls glow plug ON time
  • Test verify function permits testing of relay at 70%
    of set point (programmable 0 to 99% of set point)
  • Normal or reverse relay logic is configurable by user
  • Six switch inputs plus engine speed input provide
    versatile programming
  • Protection switch inputs (EP) can be enabled at
    preset (programmable) RPM after preset time delay
  • Two auxiliary outputs indicate status and fault codes
  • Engine status indicator displays engine failure codes
    to aid in troubleshooting engine problems

Applications

  • Industrial engines and power systems
  • Generator sets and control systems
  • Heavy equipment and machinery
  • Automation and mechanical actuation

Technical Notes

Electrical Specifications:
Power Input 9–30 VDC, reverse polarity
protected
Electromagnetic Compatibility ISO 14982:1998/E
EMI Immunity 30 V/M 20 MHz to 1000 MHz
(ISO 14982:1998/E)
Nominal Operating Current 12 Volt 24 Volt
Operating: 140 mA 120 mA
Standby: 25 mA 40 mA
Relay Contact Ratings
Resistive Load: 0.1 to 10 A @ 28 VDC
Inductive Load: 0.1 to 8 A @ 28 VDC
Auxiliary Outputs Aux 1 and Aux 2: 200 mA
maximum

Mechanical Specifications:
Operating Temperature -40˚F to +185˚F
(-40˚C to +85˚C)
Vibration 4 G’s from 40 to 2000 Hz
Shock10 G’s @ 45 Hz
Case UV, chemical resistant, and
UL 94 V-0 flame retardant.
Encapsulated for reliability
against harsh environments
Calibration Requires interface adapter
and software for calibration
setup.
Terminations Euro style terminal block
Weight .85 lbs (.386 kg)

Why Choose Traycana